| |

PULS: MCB vs eFuse – Which Is the Best Solution for Properly Securing DC Circuits?

Feb 12, 2026 - PULS MCB vs. eFuse - Which Is the Best Solution for Properly Securing DC Circuits

February 12, 2026

MCB vs eFuse: Which Is the More Reliable Protection Mechanism

By: Abdul Ücüncü, Application Engineer, PULS

This blog article compares a traditional miniature circuit breaker (MCB) and an electronic circuit breaker (ECB) with integrated eFuses, highlighting the advantages of an ECB in terms of faster and more reliable tripping without the need for peak current.

In times of unregulated transformer power supplies, traditional miniature circuit breakers (MCB) have established themselves as the main protection modules. However, when primarily switched-mode power supplies were introduced in the 1990s, they quickly replaced transformer power supplies in industrial applications.

The new technology enabled more efficient and compact power supplies that better met the increased demands of the industry. The era of transformers was thus over, but the MCBs remained and continued to be used in conjunction with switched-mode power supplies, even on the DC side. However, there are now much better and, above all, more reliable protection mechanisms, such as electronic circuit breakers.


MCB vs. eFuse

The biggest challenge is that miniature circuit breakers were originally designed for the AC-side of the application and require multiple times the nominal current for a few milliseconds to trip. Many switched-mode power supplies cannot provide this, as they shut down on the DC side during a high current pulse to protect themselves and the connected loads.

The alternative to the classic miniature circuit breaker (MCB) is an electronic circuit breaker (ECB) with integrated eFuses. These modules, such as PULS’s PISA models, are optimised for the distribution and protection of DC loads and do not require peak current for reliable and quick tripping. The reaction time, even with slight overload, is within 1 ms.

This article explains some differences between MCBs and ECBs in detail, which can help you choose the right solution.

Choosing the right MCB requires a precise understanding of the application and careful system planning. With an ECB, this effort can be significantly reduced.

Abdul Ücüncü, Application Engineer, PULS 

Approval: MCB on the DC Side Only with IEC 60947-2

Most circuit breakers were developed for the protection of AC circuits. The idea that the same technology can also protect DC circuits is a misconception.

The main reason is that the arc burning and arc extinguishing properties of AC and DC systems are different. An AC circuit breaker may not reliably trip in a DC circuit. Therefore, if you want to use an MCB on the DC side in industrial low-voltage systems, it must comply with the IEC 60947-2 standard. This standard applies to MCBs whose main contacts are intended for connection to circuits with rated voltages in the low-voltage range of 1,000 VAC or 1,500 VDC.

Feb 12, 2026 - PULS MCB vs. eFuse - Which Is the Best Solution for Properly Securing DC Circuits

Tripping Characteristic: B, C or Z?

When selecting a circuit breaker, it is important to look at the tripping characteristic. There are different tripping characteristics suitable for various industrial applications. However, to reliably protect a DC circuit, it is advisable to use an MCB with the Z tripping characteristic.

Since circuit breakers with this tripping characteristic are more expensive, MCBs with the B or C tripping characteristic are mostly used in practice. As the graph shows, circuit breakers with a Z characteristic trip at 2 to 3 times the nominal current and are significantly faster than MCBs with a B characteristic, which trip at 3 to 5 times the nominal current, or even a C characteristic, which requires 5 to 10 times the current.

With an electronic circuit breaker, the selection of the tripping characteristic is much more flexible. As part of PULS’s PISA-M series, they offer an “adjustable” version where the tripping currents and characteristics can be flexibly adjusted. Thus, the tripping speed can be chosen between a fast (max. 2 ms) and a slow (max. 10 ms) characteristic.

The current values can be individually set for each of the 4 channels, as long as the total current does not exceed 20 A. With ECBs, users can respond much more flexibly to different loads or system expansions.


Tripping Mechanism: Thermal & Magnetic or Electrical?

A circuit breaker has two types of tripping mechanisms integrated: thermal and magnetic tripping mechanisms.

The thermal fuse is responsible for tripping the circuit breaker in case of overload. Depending on the current level, tripping can take from a few seconds to 1-2 hours. The bimetal in the circuit breaker is responsible for the thermal tripping. When the current in the circuit breaker exceeds the nominal value, the bimetal heats up and deforms, triggering the shutdown mechanism. Since the current has the same thermal effect on both DC and AC sides, the thermal tripping works the same under defined environmental conditions for both DC and AC.

The magnetic fuse is responsible for the short-circuit tripping of the circuit breaker. It is supposed to trip within a few milliseconds in a specific tripping range (each tripping characteristic has its own range). The coil in the circuit breaker is responsible for this. When a very high current flows, a strong magnetic field is formed, which trips the switch.

Since the peak value of the alternating current determines the size of the magnetic field, a correction factor for the magnetic tripping must be taken into account when using a circuit breaker in DC circuits. This correction factor is √2 or 1.41. The immediate tripping ranges for circuit breakers with different tripping characteristics are described below.

An electronic circuit breaker, on the other hand, enables simpler and more precise tripping of the channels. The ECB continuously measures the current, and the integrated eFuse reliably and quickly trips at the defined current value. This process works independently of external influences, such as ambient temperature, which is a significant advantage over MCBs. An ECB directly contributes to higher system availability.

Feb 12, 2026 - PULS MCB vs. eFuse - Which Is the Best Solution for Properly Securing DC Circuits
The tripping current of MCBs is always specified as AC in the datasheet and must be multiplied by 1.41 to convert to DC values; this graphic shows the AC current and the corrected DC current.

Temperature Dependence and “Rated Diversity Factor”

As explained with the thermal fuse, the bimetal responsible for tripping is temperature-dependent. This means: the higher the ambient temperature, the more the bimetal heats up and trips earlier. High ambient temperature leads to the maximum nominal current flowing through the circuit breaker needing to be reduced to prevent unwanted tripping. Conversely, at low temperatures, a higher current must flow to sufficiently heat the bimetal to trip the circuit breaker.

The installation situation in the control cabinet can also affect the thermal fuse. When multiple circuit breakers are operated side by side without spacing, thermal interaction occurs between them. The circuit breakers heat each other, which means the maximum nominal current of the circuit breakers must be reduced again. How much the current needs to be reduced due to increased temperature of the MCB in such cases is specified by the manufacturer and referred to as the Rated Diversity Factor (RDF).

Electronic circuit breakers, on the other hand, are temperature independent. The operating temperature of the PISA-M is between -25 °C and +70 °C at full output power, i.e., without derating. A Rated Diversity Factor is not necessary.

The modules can also be installed in the control cabinet without minimum spacing to other PISA-M units. Only a minimum distance of 15 mm to heat sources, such as the power supply, must be maintained.


Choosing the Right Power Supply Unit

Just as important as selecting the right circuit breaker is the decision for the appropriate power supply unit. This aspect is often overlooked.

Practice shows that the short-circuit current of a 10 A power supply for a total load of 7 A may not be sufficient to trip the MCB and isolate the faulty load. Because with a load of 7 A, a 10 A MCB is usually used. This means that if an MCB with the B characteristic is used, the 10 A power supply would need to provide between 30 A and 50 A as short-circuit current to trip the MCB. Most 10 A power supplies cannot provide this much current, as they shut down for self-protection beforehand. As a result, all loads connected to the power supply are no longer supplied, even if they do not have a fault.

To avoid this problem, a power supply with a fuse-breaking feature can be used, which provides 5-6 times the nominal current for a few milliseconds. Alternatively, the power supply must be oversized. This means using a higher power class. Both solutions have their disadvantages: users may pay for functions they do not need, and a larger power supply requires more space in the system. Even with a perfectly matched power supply to the MCBs, it may happen that the short-circuit current is not sufficient to trip the circuit breaker – for example, if the total resistance of the short-circuit path is too high.

If you want to combine a power supply with an electronic circuit breaker, only the available maximum output current of the power supply is relevant for the decision. For an ECB of the PISA-M type, PULS recommends a power supply with at least 90 W output power. The selection is thus much more flexible.

Feb 12, 2026 - PULS MCB vs. eFuse - Which Is the Best Solution for Properly Securing DC Circuits
The 480 W DIN rail power supply CP20.248 features easy fuse breaking with 3 times the nominal current for 12 ms.

Summary

Choosing the right circuit breaker requires a precise understanding of the application and careful system planning. All this takes timeengineering resources, and ultimately money.

With every small change in the application, it must be determined again whether the circuit breakers still provide sufficient protection for the existing loads. With an electronic circuit breaker, this effort can be significantly reduced. In addition to wiring, only the configuration of the output currents needs to be done.

PULS’s PISA modules with integrated eFuses protect loads by reliably tripping affected channels, regardless of the load, temperature, power supply, or total resistance of the short-circuit path.

For more information on PULS solutions HERE

PULS MCB vs. eFuse - Which Is the Best Solution for Properly Securing DC Circuits

Source

MCB vs eFuse MCB vs eFuse MCB vs eFuse MCB vs eFuse MCB vs eFuse MCB vs eFuse MCB vs eFuse MCB vs eFuse MCB vs eFuse MCB vs eFuse MCB vs eFuse MCB vs eFuse MCB vs eFuse MCB vs eFuse MCB vs eFuse

Related Articles


Changing Scene


Sponsored Content
The Easy Way to the Industrial IoT

The way to the Industrial IoT does not have to be complicated. Whether access to valuable data is required or new, data-driven services are to be generated, Weidmuller enables its customers to go from data to value the easy way. Weidmuller’s comprehensive and cutting-edge IIoT portfolio applies to greenfield and brownfield applications. Weidmuller offers components and solutions from data acquisition, data pre-processing, data communication and data analysis.

Visit Weidmuller’s Industrial IoT Portfolio.


ADVANCED Motion Controls Takes Servo Drives to New Heights (and Depths) with FlexPro Extended Environment Product Line

Advanced Motion Controls is proud to announce the addition of six new CANopen servo drives with Extended Environment capabilities to their FlexPro line. These new drives join AMC’s existing EtherCAT Extended Environment FlexPro drives, making the FlexPro line the go-to solution for motion control applications in harsh environments.

Many motion control applications take place in conditions that are less than ideal, such as extreme temperatures, high and low pressures, shocks and vibrations, and contamination. Electronics, including servo drives, can malfunction or sustain permanent damage in these conditions.

Read More


Service Wire Co. Announces New Titles for Key Executives

Bruce Kesler and Mark Gatewood have been given new titles and responsibilities for Service Wire Co.

Bruce Kesler has assumed the role of Senior Director – Business Development. Bruce will be responsible for Service Wire’s largest strategic accounts and our growing Strategic Accounts Team.

Mark Gatewood has been promoted to the role of Vice President – Sales & Marketing. In this role, Gatewood will lead the efforts of Service Wire Company’s entire sales and marketing organization in all market verticals.

Read More


Tri-Mach Announces the Purchase of an Additional 45,000 sq ft. Facility

Tri-Mach Elmira Facility

Recently, Tri-Mach Inc. was thrilled to announce the addition of a new 45,000 sq ft. facility. Located at 285 Union St., Elmira, ON, this facility expands Tri-Mach’s capabilities, allowing them to better serve the growing needs of their customers.

Positioning for growth, this additional facility will allow Tri-Mach to continue taking on large-scale projects, enhance product performance testing, and provide equipment storage for their customers. The building will also be the new home to their Skilled Trades Centre of Excellence.

Read More


JMP Parent Company, CONVERGIX Acquires AGR Automation, Expanding Global Reach

Convergix Automation Solutions has completed the acquisition of AGR Automation (“AGR”), a UK-based provider of custom, high-performance automation design and systems integration primarily to the life sciences industry.

Following Convergix’s acquisitions of JMP Solutions in August 2021 and Classic Design in February 2022, AGR marks the third investment in Crestview’s strategy to build Convergix into a diversified automation solutions provider targeting the global $500+ billion market, with a particular focus on the $70 billion global systems integration and connectivity segments. Financial terms of the transaction were not disclosed.

Read More


Latest Articles

  • PULS: MCB vs eFuse – Which Is the Best Solution for Properly Securing DC Circuits?

    PULS: MCB vs eFuse – Which Is the Best Solution for Properly Securing DC Circuits?

    In times of unregulated transformer power supplies, traditional miniature circuit breakers (MCB) have established themselves as the main protection modules. However, when primarily switched-mode power supplies were introduced in the 1990s, they quickly replaced transformer power supplies in industrial applications. The new technology enabled more efficient and compact power supplies that better met the increased… Read More…

  • Streamline Control Cabinet Design with WSCAD ELECTRIX

    Streamline Control Cabinet Design with WSCAD ELECTRIX

    Creating intricate control cabinets can be a breeze with WSCAD ELECTRIX. The more meticulous your designing gets, the smoother and less error-prone the entire production process becomes. WSCAD ELECTRIX goes beyond with its Cabinet Expert module. This module unlocks the full potential of control cabinet engineering and empowers you to automate tasks, saving you valuable… Read More…